Operation of hyper mist system

Posted on August 21, 2024August 21, 2024 By admin No Comments on Operation of hyper mist system

Working

System consists of a freshwater tank, freshwater pump, solenoid valves, nozzle, control unit, etc.

At the time of fire, fresh water pump takes suction from fresh water tank to the sprinkler
system at high pressure.
Each area separated by isolating valves which will operate during fire.

How to Activate hyper mist system:-
It can be done by three methods

Automatic: System will start automatically when two detectors (Flame & smoke) will get
activated.
Activating from local panel: There is a push switch provided to start manually
Emergency Starting: Start the pump manually then manually open the solenoid valves

The most common areas covered by water mist system

Incinerator room
Auxiliary boiler room
Auxiliary generators
Main engine cylinder head platform
Purifier room
Inert gas generator room

The hyper mist or high-pressure fog firefighting system is installed for all important ship’s machinery systems in the engine room (ME. AE, Purifier, Boiler etc.). The high-pressure water mist/fog system provides water mist protection during emergencies to engine room areas and machinery spaces. This system is independent of any other fixed firefighting system such as foam or CO2 system.

A fresh water pump takes suction from fresh water tank to supply high-pressure water to the sprinkler system. Each area is isolated by valves, which can be opened during emergency situations involving fire. The system is kept at constant state of readiness.

The MICROFOG Fire Extinguishing System has the following effects:

 Cooling effect (quick cooling by evaporation latent heat)

 Oxygen replacement effect (replacement of air with water vapor generated in a large quantity, and absorption of radiation heat)

 Shut-off effect (the floating fog forming walls of water)

 Smoke eliminating effect (the floating smoke particles being adsorbed and settled by the fog)

High-pressure water is injected through a special nozzle working within pressure range of 4 to 10 MPa (depending upon the design of the system), which breaks the water droplets into fine mist. The diameter of the water mist particle ranges from 50 to 200 µm which improves the fire extinguishing effect and efficiency of the system. The distance between any two nozzles is very critical as area covered by one nozzle must be such that no space is left unsprayed in the fire affected area.

Operating Procedure:

The system start select switch on the main control panel must always be set to AUTO & MANUAL position for automatic start. (The automatic activation with the fire alarm system is possible only in this mode.)

Automatic Start: Water mist system will be automatically released into the protected area where fire is detected by the fire alarm system (both smoke and flame detectors), and an audible and visible alarm is activated in that protected area.

Manual Start: Water mist system can be started manually from the control panel and from the local points whenever needed, independent of the fire alarm system.

The following conditions must be maintained at all times to ensure hyper mist system is on stand by for operation:

  1. Sufficient water level must be retained in the fresh water tank
  2. Make sure the power supply is available.
  3. The fire alarm system must be in operation.
  4. Drain and test valves must be closed.
  5. The area around the Hyper mist water pump must be clear of any obstructions.

Stopping:
After confirming extinction of a fire, the water mist system can be stopped manually by cancelling the signal from the fire alarm system and pressing the STOP button on the control panel or local point

LSA & FFA Tags:areas covered by water mist system, How to Activate hyper mist system, hypermist sytem, working of hypermist

Post navigation

Previous Post: What is P& I
Next Post: Collective Bargaining Agreement

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Categories

  • Bulk Carrier
  • Cargo handling
  • Engine Room Operations
  • LSA & FFA
  • Maritime Industry
  • Maritime Law
  • Merchant Shipping
  • Navigation
  • Rules and Regulation
  • Ship Construction
  • Shipboard operation
  • Stability
  • Tanker
  • Uncategorized

Blog is primarily for candidates appearing for certificate of competency exams but such is the detail that while being equally suitable for the beginner, it is also reference work for experienced seaman, and the layout and style of blog make it suitable for shipboard training where practical experience can be allied to the theoretical approach.

Recent Comments

  • capt on Radar Best Practice -ARPA
  • admin on Dry Docking (Theory & Numericals)
  • Stelios Karamplakas on Dry Docking (Theory & Numericals)
  • Farid OMARI on Demurrage
  • admin on Tanker Cargo Calculations

Copyright © 2018 knowledge of sea – All Rights Reserved.

If you’re unsure about what type of training will work best for you, just tell us a little more about your needs. We will get back to you as soon as possible with the answers you need!

All answers will be from sailor mouth, who is practically working on board.

January 2026
S M T W T F S
 123
45678910
11121314151617
18192021222324
25262728293031
« Dec    

Copyright © 2026 Knowledge Of Sea.

Powered by PressBook WordPress theme

Go to mobile version